239
CHAPTER 4 FUNCTIONS
4
4.20 Simultaneous Temperature Rise Function
(1) Operation of the simultaneous temperature rise function
The channel with the temperature rise reaching the set value (SV) last among channels satisfying the condition
for start-up in the same group is used as a standard when the simultaneous temperature rise function is started
up. The temperature of other channels rises following the temperature of the standard channel. The standard
channel is determined based on the simultaneous temperature rise parameter and the deviation (E).
Ex.
When all channels are selected for Group 1
*1 This becomes Simultaneous temperature rise in process (1) when the temperature rise starts; however, it becomes
Simultaneous temperature rise not in process (0) before the temperature rise starts.
CH1 Set value (SV)
Matches temperature rise
completion time
Temperature process value (PV)
Time
Arrival point
CH2 Set value (SV)
CH3 Set value (SV)
CH4 Set value (SV)
Temperature rise start
CH Simultaneous
temperature rise status
(Un\G734, Un\G750,
Un\G766, Un\G782)
*1
100
Setting/operation
mode instruction (Yn1)
OFF
ON
Executed by the Q64TCN