69
CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.1 Q64TCN buffer memory assignment list
169(A9
H
)
All CHs PID continuation flag 0 R/W ×
Page 131,
Section
3.4.2 (43)
170(AA
H
)
All CHs
Heater disconnection compensation function
selection
*11
0R/W ×
Page 131,
Section
3.4.2 (44)
171(AB
H
)
System area to
174(AE
H
)
175(AF
H
)
All CHs Transistor output monitor ON delay time setting 0 R/W ×
Page 132,
Section
3.4.2 (45)
176(B0
H
)
All CHs
CT monitor method switching
*11
0R/W ×
Page 132,
Section
3.4.2 (46)
177(B1
H
)
CH1
Manipulated
value (MV) for
output with
another analog
module
Manipulated
value of
heating (MVh)
for output with
another analog
module
Manipulated
value of
heating (MVh)
for output with
another analog
module
0R × ×
Page 133,
Section
3.4.2 (47)
178(B2
H
)
CH2
Manipulated
value (MV) for
output with
another analog
module
Manipulated
value of
heating (MVh)
for output with
another analog
module
Manipulated
value of
heating (MVh)
for output with
another analog
module
*7
0R × ×
179(B3
H
)
CH3
Manipulated
value (MV) for
output with
another analog
module
Manipulated
value of
heating (MVh)
for output with
another analog
module
*6
Manipulated
value (MV) for
output with
another analog
module
0R × ×
180(B4
H
)
CH4
Manipulated
value (MV) for
output with
another analog
module
Manipulated
value of
heating (MVh)
for output with
another analog
module
*6
Manipulated
value (MV) for
output with
another analog
module
0R × ×
181(B5
H
)
All CHs
Resolution of the manipulated value for output with
another analog module
0R/W ×
Page 134,
Section
3.4.2 (48)
182(B6
H
)
All CHs
Cold junction temperature compensation selection
*8
0R/W ×
Page 135,
Section
3.4.2 (49)
183(B7
H
)
All CHs Control switching monitor 0 R × ×
Page 135,
Section
3.4.2 (50)
Address
(decimal
(hexadecimal))
Target
channel
or
current
sensor
(CT)
Setting contents
Default
value
*1
Read/
Write
*2
Automatic
setting
*3
E
2
PROM
write
availability
*4
Reference
Standard
control
Heating-
cooling
control
Mix control