Mitsubishi Electronics Q64TCTTN Network Card User Manual


 
257
CHAPTER 4 FUNCTIONS
4
4.24 Proportional Band Setting Function
4.24 Proportional Band Setting Function
Proportional band (P) values can be set for heating and cooling separately using this function. Different gradients can
be set by using different proportional band (P) values in a heating and cooling area.
(1) Setting method
(a) For heating
Set the value in CH Heating proportional band (Ph) setting (Un\G35, Un\G67, Un\G99, Un\G131).
( Page 105, Section 3.4.2 (15))
(b) For cooling
Set the value in CH Cooling proportional band (Pc) setting (Un\G720, Un\G736, Un\G752, Un\G768).
( Page 105, Section 3.4.2 (15))
Heating-cooling
Manipulated value
for cooling (MVc) 100%
Manipulated value
for heating (MVh) 0%
Manipulated value
for heating (MVh)
100%
Manipulated value
for cooling (MVc) 0%
100%
0%
Set value (SV)
Heating proportional
band (Ph)
Cooling
Heating
Cooling proportional
band (Pc)
-100%
Only cooling
proportional band (Pc)
can be narrowed.
Manipulated value
for heating (MVh)
Manipulated value
for cooling (MVc)