Mitsubishi Electronics Q64TCTTN Network Card User Manual


 
171
CHAPTER 4 FUNCTIONS
4
4.3 Control Method
(7) Buffer memory areas related to control method
The following table shows the buffer memory areas related to control method.
Buffer
memory area
name
Buffer memory address Setting range
Reference
CH1 CH2 CH3 CH4
Two-
position
control
P
control
PD
control
PI
control
PID
control
CH Input range Un\G32 Un\G64 Un\G96 Un\G128
Thermocouple: 1 to 4, 11 to 28, 36 to 48, 100 to 117, 130
to 132, 201 to 205
Platinum resistance thermometer: 5 to 8, 53, 54, 140 to
143, 201 to 205
Page 96,
Section
3.4.2 (12)
CH Set value
(SV) setting
Un\G34 Un\G66 Un\G98 Un\G130
Set a value within the temperature measurement range of
the set input range.
Page 104,
Section
3.4.2 (14)
CH
Proportional
band (P) setting
Un\G35 Un\G67 Un\G99 Un\G131
Fix the
setting to 0.
Configure the setting in the range from 0 to
10000 (0.0% to 1000.0%) toward the full
scale of the set input range.
Page 105,
Section
3.4.2 (15)
CH Heating
proportional
band (Ph) setting
Un\G35 Un\G67 Un\G99 Un\G131
CH Cooling
proportional
band (Pc) setting
Un\G720 Un\G736 Un\G752 Un\G768
The setting
is ignored.
*1
Configure the setting in the range from 1 to
10000 (0.1% to 1000.0%) toward the full
scale of the set input range.
CH Integral
time (I) setting
Un\G36 Un\G68 Un\G100 Un\G132
The setting
is ignored.
*1
Fix the
setting to
0.
Fix the
setting to
0.
1 to
3600 (s)
1 to
3600 (s)
Page 107,
Section
3.4.2 (16)
CH Derivative
time (D) setting
Un\G37 Un\G69 Un\G101 Un\G133
The setting
is ignored.
*1
Fix the
setting to
0.
1 to
3600 (s)
Fix the
setting to
0.
1 to
3600 (s)
Page 107,
Section
3.4.2 (17)
CH Upper limit
output limiter
Un\G42 Un\G74, Un\G106 Un\G138
The setting
is ignored.
*1
-50 to 1050 (-5.0% to 105.0%)
Page 110,
Section
3.4.2 (19)
CH Lower limit
output limiter
Un\G43 Un\G75 Un\G107 Un\G139
CH Heating
upper limit output
limiter
Un\G42 Un\G74 Un\G106 Un\G138
0 to 1050 (0.0% to 105.0%)
CH Cooling
upper limit output
limiter
Un\G721 Un\G737 Un\G753 Un\G769
CH Output
variation limiter
setting
Un\G44 Un\G76 Un\G108 Un\G140
The setting
is ignored.
*1
1 to 1000 (0.1%/s to 100.0%/s)
Page 112,
Section
3.4.2 (20)
CH Adjustment
sensitivity (dead
band) setting
Un\G46 Un\G78 Un\G110 Un\G142
Configure
the setting
in the range
from 1 to
100 (0.1%
to 10.0%)
toward the
full scale of
the set
input range.
The setting is ignored.
*1
Page 113,
Section
3.4.2 (22)