(86)Peak current suppression control group setting (Un\G784)
Set the target channels for the peak current suppression function and the gap of the control output cycle between
channels.
For details on the peak current suppression function, refer to the following.
Page 233, Section 4.19
(a) Setting range
•0
H
: Not divide
•1
H
: Group 1
•2
H
: Group 2
•3
H
: Group 3
•4
H
: Group 4
(b) Enablement of setting contents
Enable the setting contents by turning Setting change instruction (YnB) OFF ON OFF during the setting
mode (Setting/operation mode status (Xn1): OFF).
(c) Default value
The default value is set to Not divide (0
H
).
The division number depends on this setting. The upper limit output limiter value is automatically set to correspond to the
specified division number.
The following table lists the upper limit output limiter values which are set when this setting is enabled.
CH Lower limit output limiter (Un\G43, Un\G75, Un\G107, Un\G139) is set to 0.
Division Number
CH Upper limit output limiter (Un\G42, Un\G74, Un\G106, Un\G138)
( Page 110, Section 3.4.2 (19))
2 500 (50.0%)
3 333 (33.3%)
4 250 (25.0%)
Standard
b15 b0
to to to to
b8 b7 b4 b3b11b12
CH4 CH3 CH2 CH1