CHAPTER 7 PROGRAMMING
7
7.2 When Using the Module in a Standard System Configuration
7.2.1 Standard control (such as auto tuning, self-tuning, and error code read)
(4) Switch Setting
Configure the output setting at CPU stop error and the control mode selection as follows.
Project window [Intelligent Function Module] [Q64TCTTN] [Switch Setting]
Item
Set value
CH1 CH2 CH3 CH4
Output Setting at CPU Stop
Error
0: CLEAR 0: CLEAR 0: CLEAR 0: CLEAR
Control Mode Selection 0: Standard Control
Auto-setting at Input Range
Change
0: Disable
Setting Change Rate Limiter 0: Temperature Rise/Temperature Drop Batch Setting
Moving Averaging Process
Setting
0: Enable