Schneider Electric altivar 58 telemecanique Electronic Accessory User Manual


 
75
ENGLISH
Adjust Menu
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for high torque applications.
Code Description Adjustment range Factory setting
SS
SS
dd
dd
CC
CC
DC stop.curr - A
0.1 to 1.36 In (1) Acc. to contr. rating
Injection braking current applied after 30 seconds if tdC = Cont.
Check that motor will withstand this curr. without overheating
JJ
JJ
PP
PP
FF
FF
Jump Freq. - Hz
0 to HSP 0 Hz
Skip frequency : prohibits prolonged operation over a frequency range of +/-2.5 Hz around JPF. This
function can be used to prevent a critical speed which causes resonance.
JJ
JJ
FF
FF
22
22
Jump Freq.2 - Hz
0 to HSP 0 Hz
Second skip frequency: Same function as JPF, for a second frequency value
JJ
JJ
FF
FF
33
33
Jump Freq.3 - Hz
0 to HSP 0 Hz
Third skip frequency: Same function as JPF, for a third frequency value
UU
UU
SS
SS
CC
CC
Machine Coef.
0.01 to 100 1
Coefficient applied to parameter rFr (output frequency applied to the motor), the machine speed is
displayed via parameter USP
USP = rFr x USC
tt
tt
LL
LL
SS
SS
LSP Time - s
0 to 999.9 0 (no time limit)
Operating time at low speed. After operating at LSP for a given time, the motor is stopped
automatically. The motor restarts if the frequency reference is greater than LSP and if a run
command is still present.
Caution : value 0 corresponds to an unlimited time
GP_ATV58_EN.fm Page 75 Mardi, 2. avril 2002 6:09 18