Schneider Electric altivar 58 telemecanique Electronic Accessory User Manual


 
83
ENGLISH
Drive Menu
(1) 100% corresponds to the nominal torque of a motor with a power rating equal to that associated with the
speed controller for "high torque" applications.
(2) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
(3) Yes if SFt = LF, No if SFt = HF1 or HF2
Code Description Adjustment range Factory setting
tt
tt
LL
LL
II
II
Trq.Limit _ %
0 to 200% (1) 200%
The torque limit is used to limit the maximum motor torque.
CC
CC
LL
LL
II
II
nt. I Lim - A
0 to 1.36 In (2) 1.36 In
The current limit is used to limit motor overheating.
AA
AA
dd
dd
CC
CC
Auto DC Inj.
No-Yes Yes
Used to deactivate automatic DC injection braking on stopping.
PP
PP
CC
CC
CC
CC
Motor P Coef
0.2 to 1 1
Defines the relationship between the speed controller nominal power and a less powerful motor
when a logic input has been assigned to the motor switching function.
SS
SS
FF
FF
tt
tt
Sw Freq. Type
LF-HF1-HF2 LF
Used to select a low switching frequency (LF) or a high switching frequency (HF1 or HF2). HF1
switching is designed for applications with a low load factor without derating the speed controller. If
the thermal state of the speed controller exceeds 95 %, the frequency automatically changes to 2
or 4 kHz depending on the speed controller rating. When the thermal state of the speed controller
drops back to 70 %, the selected switching frequency is re-established. HF2 switching is designed
for applications with a high load factor with derating of the speed controller by one rating : the drive
parameters are scaled automatically (torque limit, thermal current, etc).
Modifying this parameter results in the following parameters returning to factory
settings :
• nCr, CLI, Sfr, nrd (Drive menu)
• ItH, IdC, Ibr, Ctd (Adjust menu).
SS
SS
FF
FF
rr
rr
Sw Freq. - kHz
0.5-1-2-4-8-12-16 kHz acc. to controller rating
Used to select the switching frequency. The adjustment range depends on the SFt parameter.
If SFt = LF : 0.5 to 2 or 4 kHz acc. to the controller rating
If SFt = HF1 or HF2 : 2 or 4 to 16 kHz acc. to the controller rating
The maximum operating frequency (tFr) is limited according to the switching frequency :
nn
nn
rr
rr
dd
dd
Noise Reduct
No-Yes (3)
This function modulates the switching frequency randomly to reduce motor noise.
SS
SS
PP
PP
CC
CC
Special motor
No-Yes No
This function with "yes" extends the adjustment range for the UFr parameter in the adjust menu for
adaptation to the special motors mentioned at the start of this section. Can only be accessed in the
"Handling" and "General use" macro-configurations.
NO : normal motor
YES : special motor
PSM : small motor
SFr(kHz)
0.5 1 2 4 8 12 16
tFr (Hz)
62 125 250 500 500 500 500
GP_ATV58_EN.fm Page 83 Mardi, 2. avril 2002 6:09 18