Adjust Menu
Code Description Adjustment range Factory setting
PP
PP
SS
SS
PP
PP
PI Filter - s
0,0 à 10,0 0 s
Adjusts the time constant of the filter on the return PI
PP
PP
II
II
22
22
PI Preset 2 - %
0 à 100 % 30 %
2nd preset reference of PI when a logic input has been assigned to 4 preset speeds.
100 % = maxi process
0 % = mini process
PP
PP
II
II
33
33
PI Preset 3 - %
0 à 100 % 60 %
3rd preset reference of PI when a logic input has been assigned to 4 preset speeds.
100 % = maxi process
0 % = mini process
dd
dd
tt
tt
dd
dd
ATV Th. fault
0 à 118 % 105 %
Level of drive thermal state above which the logic output or relay change to state 1.
GP_ATV58_EN.fm Page 80 Mardi, 2. avril 2002 6:09 18