HP (Hewlett-Packard) HP RP7405/7410 Network Card User Manual


 
Appendix B
System Specifications
Electrical Specifications
96
System Power Specifications
Table B-4 and Table B-5 list the AC power requirements for an hp rp7405/rp7410 server. These tables provide
information to help determine the amount of AC power needed for your computer room.
Future upgrades may increase the Maximum Theoretical System Power to 3400 VA.
Maximum power is the sum of the worst case power consumption of every subsystem in the box, and should
be used to size worst case power consumption for facility installation. Typical power consumption numbers
are what HP engineers have measured running power intensive applications. These are generally lower than
maximum power numbers due to the fact that getting all of the subsystems in the box to simultaneously draw
maximum power for long durations being uncommon.
Table B-4 AC Power Specifications
Requirements Value Comments
Nominal input voltage 200, 208, 220, 240 VAC
Minimum Operating Voltage 180 VAC
Maximum Operating Voltage 269 VAC
Frequency range (minimum -
maximum)
50 - 60 (Hz)
Number of phases 1
Rated line current 12 A rms
Maximum inrush current 30 A peak for 15 ms Per line cord
Dropout carry-through time at
minimum line voltage
20 ms
Circuit breaker rating 20 A Per line cord
Branch Circuit Breaker (Size,
Type)
20A, slow trip delay
type
Power factor correction >0.97 @269VAC
>0.93 @262VAC
At all loads of 50% - 100% of
supply rating
At all loads 0f 30% - 50% of
supply rating
Ground leakage current (mA) <3.0 (ma) Per line cord
kVA rating 2.7 KVA
Table B-5 System Power Requirements
Power Required (50 - 60 Hz) VA Comments
Maximum configuration hp rp7405/rp7410 server PA8700 3000 Theoretical
Typical configuration hp rp7405/rp7410 server PA8700 1700 Typical