Lantronix XSENSO 21R2 Switch User Manual


 
14: Tunnel and Modbus Settings
xSenso User Guide 75
Modbus Settings
The Modbus server, if enabled, is active on TCP port 502. If present, the additional TCP port is
also used. Modbus TCP parameters are configured using the Modbus menu and submenus under
Admin.
Table 14-2 Modbus Settings
To Configure Modbus Settings
Using Web Manager
To configure the Modbus, go to the Admin tab/page and click Modbus in the menu.
Using the CLI
To enter the Modbus command level: enable -> config -> modbus
Using XML
Include in your file: <configgroup name="modbus">
Supported Modbus TCP/IP Functions and Registers
Table 14-3 0xxxx Read/Write Coils (Function Codes 1, 5 and 15)
Modbus Settings Description
TCP Server State Click to turn the TCP server state On or Off. The TCP port is 502.
Additional TCP Server Port
If present,
the Modbus server also listens on this TCP port.
Response Timeout Enter the amount of time, in milliseconds, where the Modbus server will
timeout in lieu of a response.
RSS Trace Input Click to turn RSS trace input On or Off. If RSS trace input is enabled, each
PDU received on the Modbus serial line creates a non-persistent
descriptive item in the RSS feed.
Device Address Modbus Address Description
00001 0x0000 0: Relay 1 Off, 1: Relay 1 On
00002 0x0001 0: Relay 2 Off, 1: Relay 2 On
00003 0x0002 Write 1 to reset latched Relay 1
00004 0x0003 Write 1 to reset latched Relay 2