Mitsubishi Electronics FR-S500 Power Supply User Manual


 
2
Standard connection diagram and terminal specifications
1.1 Standard connection diagram and terminal
specifications
1.1.1 Standard connection diagram
Three-phase 200V power input
Three-phase 400V power input
REMARKS
*1. The N/- terminal is not provided for the FR-S520E-0.1K to 0.75K-NA.
*2. The PR terminal is provided for the FR-S520E-0.4K to 3.7K-NA. (not used)
*3. You can switch the position of sink and source logic. Refer to page 23.
*4. When the setting potentiometer is used frequently, use a 2W1k potentiometer.
*5. The terminal functions change with input terminal function selection (Pr. 60 to Pr. 63). (Refer to page 98.)
(RES, RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, X14, X16, (STR) signal selection)
*6. The terminal function changes according to the setting of output terminal function selection (Pr. 64, Pr. 65).
(Refer to page 100.) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, Y93, Y95, LF, ABC signal selection)
CAUTION
To prevent a malfunction due to noise, keep the signal cables more than 10cm away
from the power cables.
Inverter
Motor
IM
U
V
W
RUN
SE
Running
Alarm output
Operation status
output
Open
collector
Open collector
outputs
A
B
C
Frequency setting
potentiometer
1/2W1k
Frequency setting signals (Analog)
10
2
2
3
1
4 to 20mADC(+)
4
0 to 5VDC
0 to 10VDC
5
Current input(-)
(+5V)
(Common)
(4 to 20mADC)
Selected
output
common
Low speed
RL
NFB MC
Power factor improving
DC reactor
(FR-BEL: Option)
Jumper:
Remove this
jumper when FR-BEL
is connected.
P1
SINK
SOURCE
Multi-speed
selection
Take care not to short
terminals PC-SD.
RS-485
Connector
Three-phase AC
power supply
Control circuit terminalMain circuit terminal
When using the current input as
the frequency setting signal, set
"4" in any of Pr. 60 to Pr. 63 (input
terminal function selection), assign
AU (current input selection) to any
of terminals RH, RM, RL and STR
and turn on the AU signal.
Control input
signals
(No voltage
input allowed)
STF
STR
RM
Forward rotation start
Reverse rotation start
Middle speed
High speed
RH
AM
5
(+)
(-)
Analog signal
output
(0 to 5VDC)
Ground
Ground
External transistor common
24VDC power supply
Contact input common (source)
SD
PC
Contact input common
*5
*3
*5
*5
*5
*6
*6
*6
*6
*1
*2
*4
PR
R/L1
S/L2
T/L3
P/+
N/-