Mitsubishi Electronics FR-S500 Power Supply User Manual


 
170
Specification list
4.1 Specification list
4.1.1 Ratings
(1) Three-phase 200V power supply
*1. The applied motor capacity indicated is the maximum capacity applicable for use of the
Mitsubishi 4-pole standard motor.
*2. The rated output capacity indicated assumes that the output voltage is 230V.
*3. The % value of the overload current rating indicates the ratio of the overload current to the
inverter's rated output current.
For repeated duty, allow time for the inverter and motor to return to or below the
temperatures under 100% load.
*4. The maximum output voltage does not exceed the power supply voltage. You can set the
maximum output voltage to any value below the power supply voltage. However, the
pulse voltage value of the inverter output side voltage remains unchanged at about
that of the power supply.
*5. The power supply capacity changes with the values of the power supply side inverter
impedances (including those of the input reactor and cables).
Type FR-S520E- K-NA
0.1 0.2 0.4 0.75 1.5 2.2 3.7
Applied motor capacity (*1)
kW 0.1 0.2 0.4 0.75 1.5 2.2 3.7
HP 1/8 1/4 1/2 1 2 3 5
Output
Rated capacity (kVA) (*2) 0.3 0.5 1.0 1.6 2.8 4.0 6.6
Rated current (A) 0.8 1.4 2.5 4.1 7.0 10 16.5
Overload current rating (*3) 150% 60s, 200% 0.5s (inverse time characteristics)
Voltage (*4) Three-phase 200 to 240V
Power supply
Rated input AC voltage/frequency Three-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage fluctuation 170 to 264V 50Hz/60Hz
Permissible frequency fluctuation Within ±5%
Power supply system capacity
(kVA) (*5)
0.4 0.7 1.2 2.1 4.0 5.5 9
Protective structure (JEM1030) Enclosed type (IP20)
Cooling system Self-cooling Forced air cooling
Approximate mass (kg (lbs))
0.5
(1.1)
0.5
(1.1)
0.8
(1.76)
0.9
(1.98)
1.5
(3.3)
1.5
(3.3)
2.1
(4.62)
2