74
Explanation of functions (parameters)
2.3.10 Jog operation (Pr.15 , Pr.16 )
Set the frequency and acceleration/deceleration time for jog operation.
2.3.11 RUN key rotation direction selection (Pr.17 )
Refer to (page 65)
Refer to , (page 67)
To start/stop jog operation in the
external operation mode, choose the
jog operation function in input terminal
function selection, turn on the jog
signal, and turn on/off the start signal
(STF, STR).
You can choose the jog operation
mode from the parameter unit (FR-
PU04) and perform jog operation
using the or .
(Can be read as the basic parameters when the FR-PU04 is connected.)
Parameter Name Factory Setting Setting Range Remarks
15 Jog frequency 5Hz 0 to 120Hz
Setting is enabled when
Pr. 30 = "1".
16
Jog acceleration/
deceleration time
0.5s 0 to 999s
CAUTION
In S-shaped acceleration/deceleration pattern A, the acceleration/deceleration
time is the period of time required to reach Pr. 3 "base frequency", not Pr. 20
"acceleration/deceleration reference frequency".
The acceleration time and deceleration time cannot be set separately for jog
operation.
The Pr. 15 "Jog frequency" value should be equal to or higher than the Pr. 13
"starting frequency" setting.
Assign the jog signal using any of Pr. 60 to Pr. 63 (input terminal function
selection).
Related parameters
Assignment of jog signal to terminal Pr. 60 to Pr. 63 (input terminal function selection)
(refer to page 98)
Acceleration/deceleration pattern S-shaped acceleration/deceleration A
Pr. 29 "acceleration/deceleration pattern" (refer to page 79)
Used to choose the direction of rotation by operating the key of the operation
panel.
Parameter Name
Factory
Setting
Setting
Range
Remarks
17
RUN key rotation
direction selection
00, 1
0: Forward rotation
1: Reverse rotation
Setting is enabled
when Pr. 30 = "1".
FWD
REV
O
utput frequency (Hz)
ON
Pr.20
Forward
rotation
Pr.16
Jog frequency
setting range
Pr.15
JOG signal
STF signal
ON
RUN
RUN