Parameter Instruction Code List
APPENDIX 1 Parameter Instruction Code List
The extended function parameters are made valid by setting "1" in Pr. 30 "extended
function display selection".
Func-
tion
Parameter
Number
Name
Instruction
Code
Computer
Link Data
Setting
Increments*
Link Parameter
Extension
Setting
(Instruction
Code 7F/FF)
Read Write
Basic functions
0 Torque boost 00 80 0.1% 0
1 Maximum frequency 01 81 0.01Hz 0
2 Minimum frequency 02 82 0.01Hz 0
3 Base frequency 03 83 0.01Hz 0
4
Multi-speed setting (high
speed)
04 84 0.01Hz 0
5
Multi-speed setting
(middle speed)
05 85 0.01Hz 0
6
Multi-speed setting (low
speed)
06 86 0.01Hz 0
7 Acceleration time 07 87 0.1s 0
8 Deceleration time 08 88 0.1s 0
9
Electronic thermal O/L
relay
09 89 0.01A 0
30
Extended function
display selection
1E 9E 1 0
79
Operation mode
selection
4F None 1 0
Func-
tion
Parameter
Number
Name
Instruction
Code
Computer
Link Data
Setting
Increments *
Link Parameter
Extension Setting
(Instruction
Code 7F/FF)
Read Write
Standard operation functions
10
DC injection brake
operation frequency
0A 8A 0.01Hz 0
11
DC injection brake
operation time
0B 8B 0.1s 0
12
DC injection brake
voltage
0C 8C 0.1% 0
13 Starting frequency 0D 8D 0.01Hz 0
14 Load pattern selection 0E 8E 1 0
15 Jog frequency 0F 8F 0.01Hz 0
16
Jog acceleration/
deceleration time
10 90 0.1s 0
17
RUN key rotation
direction selection
11 91 1 0
19 Base frequency voltage 13 93 0.1V 0
20
Acceleration/deceleration
reference frequency
14 94 0.01Hz 0
21
Stall prevention function
selection
15 95 1 0
22
Stall prevention operation
level
16 96 0.1% 0