Mitsubishi Electronics FR-S500 Power Supply User Manual


 
156
Errors (Alarms)
3.1 Errors (Alarms)
If any fault has occurred in the inverter, the corresponding protective function is
activated to bring the inverter to an alarm stop and automatically give the
corresponding error (alarm) indication on the PU display.
If your fault does not correspond to any of the following errors or if you have any other
problem, please contact your sales representative.
Retention of alarm output signal ..... When the magnetic contactor (MC) provided on
the power supply side of the inverter is opened
at the activation of the protective function, the
inverter's control power will be lost and the
alarm output will not be held.
Alarm indication .............................. When the protective function is activated, the
operation panel display automatically switches
to the above indication.
Resetting method............................ When the protective function is activated, the
inverter output is kept stopped. Unless reset,
therefore, the inverter cannot restart. Switch
power off once, then on again; or apply RES
signal for more than 0.1s. If the RES signal is
kept on, "Err." appears (flickers) to indicate that
the inverter is in a reset status.
When the protective function is activated, take the appropriate corrective action,
then reset the inverter, and resume operation.