Mitsubishi Electronics FR-S500 Power Supply User Manual


 
11
1
WIRING
Main circuit terminals
3) Single-phase 100V power input
*2. For installations in the United States or Canada, the circuit breaker must be inverse
time or instantaneous trip type.
*3. The power factor may be slightly lower.
*4. When the breaker on the inverter primary side trips, check for the wiring fault (short
circuit), damage to internal parts of the inverter, etc. Identify the cause of the trip,
then remove the cause and power on the breaker.
*5. The single-phase 100V power input model does not allow the power factor improving
DC reactor to be fitted.
Motor
Output
(kW
(HP))
Applied Inverter
Type
No-fuse Breaker
(NFB *1, 4) or
Earth Leakage
Circuit Breaker
(ELB) (Refer to
page 12) (*2, 4)
Magnetic
Contactor
(MC)
(Refer to
page 16)
Power Factor
Improving AC
Reactor
(Refer to page
17) (*3)
Power Factor
Improving DC
Reactor
(Refer to page
17) (*5)
0.1
(1/8)
FR-S510WE-0.1K-NA
30AF/10A S-N10 FR-BAL-0.75K
0.2
(1/4)
FR-S510WE-0.2K-NA
30AF/15A S-N10 FR-BAL-1.5K
0.4
(1/2)
FR-S510WE-0.4K-NA
30AF/20A
S-N20,
S-N21
FR-BAL-2.2K
0.75
(1)
FR-S510WE-0.75K-NA
30AF/30A
S-N20,
S-N21
FR-BAL-3.7K
*1. •Select the NFB according to the inverter power
supply capacity.
•Install one NFB per inverter.
INV
NFB INV
IM
IM
NFB