Mitsubishi Electronics FR-S500 Power Supply User Manual


 
51
Function (Parameter) list
2
FUNCTIONS
Parameter List
Output terminal functions
41
Up-to-
frequency
sensitivity
0 to 100% 1% 10% 86
42
Output
frequency
detection
0 to 120Hz 0.1Hz 6Hz 87
43
Output
frequency
detection for
reverse
rotation
0 to 120Hz, - - - 0.1Hz - - - 87
Second functions
44
Second
acceleration/
deceleration
time
0 to 999s 0.1s 5s 67
45
Second
deceleration
time
0 to 999s, - - - 0.1s - - - 67
46
Second
torque boost
0 to 15%, - - - 0.1% - - - 63
47
Second V/F
(base
frequency)
0 to 120Hz, - - - 0.1Hz - - - 65
Current detection
48
Output current
detection level
0 to 200% 1% 150% 88
49
Output current
detection
period
0 to 10s 0.1s 0s 88
50
Zero current
detection
level
0 to 200% 1% 5% 89
51
Zero current
detection
period
0.05 to 1s 0.01s 0.5s 89
Func-
tion
Para-
meter
Indica-
tion
Name Setting Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Cus-
tomer
Setting