Main circuit terminals
1.2.2 Cables, wiring length, and crimping terminals
The following table indicates a selection example for the wiring length of 20m (65.62
feet).
1) Three-phase 200V power input
2) Three-phase 400V power input
3) Single-phase 100V power input
Wiring length
100m (328.08 feet) maximum. (50m (164.04 feet) maximum for the FR-S540E-
0.4K-NA.)
Applied Inverter
Ter-
minal
Screw
size
Tight-
ening
Torque
N
⋅
m
Crimping
Terminal
Cable
PVC Insulation
Cable
mm
2
AWG
mm
2
R, S, T U, V, W
R, S, T
U, V, W
R, S, T
U, V, W
R, S, T
U, V, W
FR-S520E-0.1K
to 0.75K-NA
M3.5 1.2 2-3.5 2-3.5 2 2 14 14 2.5 2.5
FR-S520E-
1.5K, 2.2K-NA
M4 1.5 2-4 2-4 2 2 14 14 2.5 2.5
FR-S520E-
3.7K-NA
M4 1.5 5.5-4 5.5-4 3.5 3.5 12 12 4 2.5
Applied Inverter
Ter-
minal
Screw
size
Tight-
ening
Torque
N
⋅
m
Crimping
Terminal
Cable
PVC Insulation
Cable
mm
2
AWG
mm
2
R, S, T U, V, W R, S, T U, V, W R, S, T U, V, W R, S, T U, V, W
FR-S540E-0.4K
to 3.7K-NA
M4 1.5 2-4 2-4 2 2 14 14 2.5 2.5
Applied Inverter
Termi-
nal
Screw
size
Tight-
ening
Torque
N
⋅
m
Crimping
Terminal
Cable
PVC Insulation
Cable
mm
2
AWG
mm
2
R, S U, V, W R, S U, V, W R, S U, V, W R, S U, V, W
FR-S510WE-
0.1K
to 0.4K-NA
M3.5 1.2 2-3.5 2-3.5 2 2 14 14 2.5 2.5
FR-S510WE-0.75K-
NA
M4 1.5 5.5-4 2-4 3.5 2 12 14 4 2.5
CAUTION
•When the wiring length of the 0.1K and 0.2K of the three-phase 200V and
single-phase 100V class and the 0.4K and 0.75K of the three-phase 400V class
is 30m (98.43 feet) or more, set the carrier frequency to 1kHz.
•When automatic torque boost is selected in Pr. 98 "automatic torque boost
selection (motor capacity)", the wiring length should be 30m (98.43 feet)
maximum. (Refer to page 121.)