Explanation of functions (parameters)
2.3.8 Starting frequency (Pr. 13 )
The starting frequency at
which the start signal is
turned on can be set in the
range 0 to 60Hz.
Parameter Name
Factory
Setting
Setting
Range
Remarks
13 Starting frequency 0.5Hz 0 to 60Hz Setting is enabled when Pr. 30 = "1".
CAUTION
The inverter will not start if the frequency setting signal is less than the value
set in Pr. 13 "starting frequency".
For example, when 5Hz is set in Pr. 13, the motor will not start running until the
frequency setting signal reaches 5Hz.
CAUTION
Note that when Pr. 13 is set to any value lower than Pr. 2 "minimum
frequency", simply turning on the start signal will run the motor at the
preset frequency even if the command frequency is not input.
Related parameters
Minimum frequency setting Pr. 2 "minimum frequency" (refer to page 64)
Output frequency
(Hz)
60
Pr.13
Frequency setting signal (V)
Setting range
Foward rotation
ON
0
Time