54
Function (Parameter) list
Parameter List
Operation selection
functions
70
Soft-PWM
setting
Presence/absence of
Soft-PWM control can
be selected.
When Soft-PWM is
valid, the metallic tone
of motor noise can be
changed into
unoffending composite
tone.
0: Soft-PWM invalid
1: Soft-PWM valid
11103
71 Applied motor
0, 100:
Thermal characteristic
for Mitsubishi
standard motor
1, 101:
Thermal characteristic
for Mitsubishi
constant-torque motor
(Thermal characteristic
for Mitsubishi constant-
torque motor is
selected with the RT
signal ON when 100
and 101 are set.)
1069
72
PWM
frequency
selection
0 to 15 1 1 103
73
0-5V/0-10V
selection
0: For 0 to 5VDC input
1: For 0 to 10VDC input
10104
74
Input filter
time constant
0:2-step moving
average processing
1 to 8:
Exponential
average value of 2n
at the setting of n
11105
Func-
tion
Para-
meter
Indica-
tion
Name Setting Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Cus-
tomer
Setting