59
Function (Parameter) list
2
FUNCTIONS
Parameter List
Communication Parameters
Func
tion
Parame-
ter
Indica-
tion
Name Setting Range
Minimum
Setting
Incre-
ments
Factory
Setting
Refer
To:
Cus-
tomer
Setting
Communication Parameters
n1 (331)
Communication
station number
0 to 31: Specify
the station
number of the
inverter.
10132
n2 (332)
Communication
speed
48: 4800bps,
96: 9600bps,
192: 19200bps
1 192 132
n3 (333) Stop bit length
0, 1: (Data length 8),
10, 11: (Data
length 7)
11132
n4 (334)
Parity check
presence/
absence
0:Absent,
1:With odd parity
check,
2:With even
parity check
12132
n5 (335)
Number of
communication
retries
0 to 10, - - - 1 1 132
n6 (336)
Communication
check time
interval
0 to 999s, - - - 0.1s - - - 132
n7 (337)
Waiting time
setting
0 to 150ms, - - - 1 - - - 132
n8 (338)
Operation
command source
0:Command
source is
computer,
1:Command
source is
external
terminal
10147
n9 (339)
Speed command
source
0:Command
sourse is
computer,
1:Command
source is
external
terminal
10147
n10
(340)
Link startup
mode selection
0: As set in Pr. 79.
1: Started in
computer link
operation mode.
10148
n11
(341)
CR/LF selection
0:Without CR/LF,
1:With CR,
without LF
2:With CR/LF
11132
n12
(342)
E
2
PROM write
selection
0:Write to RAM
and E
2
PROM
1:Write to RAM
only
10150