Quatech INTERBUS S Network Card User Manual


 
Analog Inputs 750-476, 478
4;13614<<< :$*2®,22®6<67(0
4
The numerical format
All analog values will be shown in a unit numerical format. The resolution for 750-476
and 750-478 is 15 Bit plus sign.
750-476, -478
Input voltage Value Status LED
0-10V ±10V Binary Hex. Dec. (hex)
error
I (1,2)
>11 >11 0111 1111 1111 1111 0x7FFF 32767 0x42 on
>10,5 >10,5 0111 1111 1111 1111 0x7FFF 32767 0x42 off
10 10 0111 1111 1111 1111 0x7FFF 32767 0x00 off
5 5 0100 0000 0000 0000 0x4000 16384 0x00 off
2,5 2,5 0010 0000 0000 0000 0x2000 8192 0x00 off
1,25 1,25 0001 0000 0000 0000 0x1000 4096 0x00 off
0,0781 0,0781 0000 0001 0000 0000 0x0100 256 0x00 off
0,049 0,049 0000 0000 0001 0000 0x0010 16 0x00 off
0,0003 0,0003 0000 0000 0000 0001 0x0001 1 0x00 off
0 0 0000 0000 0000 0000 0x0000 0 0x00 off
<-0,5 0000 0000 0000 0000 0x0000 0 0x41 off
<-1 0000 0000 0000 0000 0x0000 0 0x41 on
-5 1100 0000 0000 0000 0xC000 49152 0x00 off
-10 1000 0000 0000 0000 0x8000 32768 0x00 off
<-10,5 1000 0000 0000 0000 0x8000 32768 0x41 off
<-11 1000 0000 0000 0000 0x8000 32768 0x41 on