Analog Outputs 750-550,580
:$*2Ç,2 Ç6<67(0
3
The numerical format for Siemens
In addition to the full 16 bit indication of the measured value it is possible to use the
‘Siemens format’. The measured value is represented by the most significant 12 Bits.
The 3 least significant Bits are reserved for diagnostic and status purposes. (750-580)
Output
voltage
0-10 V
Binary value
Hex. Dec.
> 10 0101 0000 0000 XXXX 50 01 20481
10 0100 0000 0000 XXXX 40 00 16384
7.5 0011 0000 0000 XXXX 30 00 12288
5 0010 0000 0000 XXXX 20 00 8192
2.5 0001 0000 0001 XXXX 10 08 4104
1.25 0000 1000 0000 XXXX 800 2048
0 0000 0000 0000 XXXX 0 0
If you have questions about the formatting of this data, please contact WAGO for
I/O System technical support.