Analog Outputs 750-552, 554, 584
:$*2Ç,2 Ç6<67(0
3
The numerical format for Siemens
In addition to the full 16 bit indication of the measured value it is possible to use the
‘Siemens format’. The measured value is represented by the most significant 12 Bits.
The 4 least significant Bits have no function. (750-584)
Output
current 4-20
mA
Binary value
Hex. Dec.
20 0100 0000 0000 XXXX 40 00 16384
16 0011 0000 0000 XXXX 30 00 12288
12 0010 0000 0000 XXXX 20 00 8192
8 0001 0000 0000 XXXX 10 00 4096
4.015 0000 0000 0001 XXXX 00 10 16
4 0000 0000 0000 XXXX 00 00 0
If you have questions about the formatting of this data, please contact WAGO for
I/O System technical support.