Quatech INTERBUS S Network Card User Manual


 
Input for thermocouple modules 750-462,469
:$*2Ç,2 Ç6<67(0
3
Temperature Ranges of the connectable sensors:
L -25°C....+900°C
K -100°C...1370°C (Default)
J -100°C...+1200°C 750-462/000-006 750-469/000-006
E -100°C...1000°C 750-462/000-008 750-469/000-008
T -100°C...+400°C 750-462/000-002 750-469/000-002
N -100°C...+1300°C 750-462/000-009 750-469/000-009
U -25°C...+600°C 750-462/000-011 750-469/000-011
B 600°C...+1800°C 750-462/000-007 750-469/000-007
R 0°C...+1700°C 750-462/000-010 750-469/000-010
S 0°C...+1700°C 750-462/000-001 750-469/000-001
mV-Meter -120 mV...+120 mV 750-462/000-003 750-469/000-003
Table 1: Temperature ranges of the connectable sensors
Attention: The range of the mV Meter is 0 to 120mV at the moment!
LED functions:
green LED: Function
ON: Normal
OFF: Watchdog-Timer Overflow
If the PLC does not transmit processing data for 100 ms the green LED
stops lightning.
red LED: Error
ON: Over- or underrange or broken wire (bei 750-469)
OFF: voltage is in the measuring range