9·18
Turn master module and slave module
power “OFF.”
Remove the setting switch cover of
network module JW-20CM.
·With your fingertips over the top and bottom
of the switch cover, pull the cover towards
you to remove it.
· Keep the cover saved as it must be installed
after switch setting.
Set MODE (function) switch
· In case of master station, be sure to setting “1.”
· In case of slave station, be sure to setting “2” or “3.”
Do not set “4 to F.”
Set STA. NO. (station number) switch
· In case of master station, be sure to setting
“00
(8)
.”
· In case of slave station, set 01 to 77
(8)
in order
“01” continuously.
A maximum number of 63 slave stations can
be connected. Enter station numbers using
octal notation.
Be careful not to assign the same number
twice and do not skip any numbers.
To the next page
eulavgnitteS noitcnuF
0yreviledtateS
1O/IetomeR
2
dradnats(knilataD
)noitcnuf
knilretupmoC
3
yromem(knilataD
)noitcnufevasyticapac
knilretupmoC
F-4
edomtseT
esulliwnamecivresA
rofsehctiwseseht
.tnemtsujda
MODE
STA.NO.
X10
X1