(I/O error code of JW model)
When error numbers 98 through 9C
(H)
occur, the module will store “rack No.” and “slot No.” in the
parameter address 005000
(8)
in the JW-20RS.
When more than one module has and error, the lowest “rack No.” and “slot No.” will be stored.
•A special I/O module error (9B
(H)
) can be detected by the JW-2DA/8AD/11DU/12DU/12PM. When
the JW-2DA/12PM detects this error, you can also assume that there is a problem in the 24 V
power supply.
•A fuse blown error (9C
(H)
) can be detected by JW-12S/13S/32S/33S/35S.
If the error cannot be eliminated after replacing the module in which the error occurred, check the
modules in the JW-20RS and then in the rack panel.
PC body and JW-20CM, JW-20RS
The operating status of the remote master station and slave stations will vary according to the
operation, stop, error, and power failure conditions in the PC as follows. For output hold switch in
detail, see page 8·15
When the JW-20RS fault lamp is lit and no error code is displayed, it might be the case that
the PC has stopped operation (in the program mode).
Parameter address D7 D6 D5 D4 D3 D2 D1 D0
005000(8)
Rack No. Slot No.
Hold
Reset
Reset
Reset
Not fixed
Not Fixed
Condition of output module
Operating at normal
Stop at normal
Error
Remote master
station error
PC power in OFF
Close
Open
Open
Open
Open
SDRD CD TEST FAULT S0 to
S7
JW-20RS Indication lamps
ERRORCOMM
PC body
operational
condition
Power supply
module
Halt
output
HALT
Power
lamp
POWER
Output hold
switch “HOLD”
Output hold switch
“RST”
Reset
Reset
Reset
Reset
Error
code
Error
code
Error
code
Operating at normal
Stop at normal
Error
Remote master
station error
Close
Open
Open
Open
SDRD CD
TEST
FAULT S0 to
S7
JW-20CM Indication lamps
ON
ON
Not fixed
Not fixed
ERRORCOMM
PC body
operational
condition
Hold
Hold
Hold
Hold
Power supply
module
PC body
Halt
output
HALT
Power
lamp
POWER
Indicator
Operating
RUN
Error
FAULT
Flag
relay
System
memory
#170 to
#177
: Light ON, : Blinks, No mark: Lights OFF
80 40 20 10
8 4 2
Measure
Cause
Register I/O table
Replace the JW-20RS
Replace basic rack panel,
extension cable, I/O
module, or register I/O
table.
Replace the fuse
1
97
(H)
98
(H)
99
(H)
9A
(H)
9B
(H)
9C
(H)
Error
code
(HEX)
LED name
I/O table error
Input data parity error
Output data error
I/O table registration error
Special I/O module error
Blown fuse