Sharp JW-20RS Computer Hardware User Manual


 
8·33
Display the contents of parameter
address 003777 by hexadecimal.
Stop PC operation
Select initial mode
Select parameter setting mode.
Screen display of JW-13PG
Write
00
(H).
03775 HEX 00
03776 HEX 00
I PARAM.
>03777 HEX 00
Parameter
setting
Turn “ON” the power of master module
Connect support tools
· Connect a support tool with the JW-20CM
master module and prepare the setting
parameter.
<Usable support tools>
JW-13PG/12PG
JW-50SP
JW-50PG, Z-100LP2S
· For operation of each support tool, see the instruction manual attached. The following describes
an example of JW-13PG’s key operation.
Stop PC operation
· Turn to program mode (stop PC operation). Setting of parameters is only available when the PC
is in program mode.
(Operation example of JW-13PG)
Stop operation of remote I/O [HEX (hexadecimal), byte]
·Setting of the parameter is only available when the operation of the JW-20CM is stopped.
·Write “00
(H)
” to parameter address 007777
(8)
and stop operation of the JW-20CM.
(Operation example of JW-13PG)
Reference Function of JW-13PG
key: Changeover unit of figures
HEX (hexadecimal)
OCT (octal)
DCM (decimal) Bit pattern
key: Byte display Changeover word display
To the next page