ambient temperature sensor. Select "None", or the temperature probe (SMTemp8 T8 / ... /
SMTemp8 T1 / ... / SMTemp1 T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1).
You can also select Maximum or Average which takes the maximum or average reading of
the temperature probes (any of SMTemp8 T8 / ... / SMTemp8 T1 / ... / SMTemp1 T8 / ... /
SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1) set as ambient temperature probes.
Amb Temp High2: Allows you to set a high ambient temperature alarm 2 point.
Amb Temp High1: Allows you to set a high ambient temperature alarm 1 point.
Amb Temp Low: Allows you to set a low ambient temperature alarm point.
System Temp1: Not used.
System Temp2: Not used.
System Temp3: Not used.
IB2 Temp1: Sets temperature port 1 on the IB2 board to None, Battery, or Ambient.
IB2 Temp2: Sets temperature port 2 on the IB2 board to None, Battery, or Ambient.
EIB Temp1: Sets temperature port 1 on the EIB board to None, Battery, or Ambient.
EIB Temp2: Sets temperature port 2 on the EIB board to None, Battery, or Ambient.
Note: You can set High2, High1, and Low temperature alarms for each temperature sensor
(from the Web Interface). Note that you cannot set high and low temperature alarms for
individual temperature sensors from the Local Menus. High and low temperature alarm
settings for the temperature sensors set as ambient are found in the Device Information
/ Power System / Settings tab. High and low temperature alarm settings for the probes
set as battery are found in the Device Information / Battery Group / Settings tab.
Power Split Menu
See also 2.7 Power Split Feature.
Menu Navigation: Main Menu / Settings / Power System / Power Split
Note: For WEB Interface; menu items are found under Device Information / Power System /
Settings Tab.
"Power Split" Parameter Settings:
Slave Curr Lmt: Current limit point for power system designated as the slave system in a
"Power Split" configuration.
Delta Volt: The offset voltage that the power system designated as the slave system in a
"Power Split" configuration is set to. It is suggested to leave this value at the default (0.5
volts).
Proportion Coeff: The proportional coefficient that the power system designated as the
slave system in a "Power Split" configuration is set to. It is suggested to leave this value at
the default (30%).
Integral Time: The integral time that the power system designated as the slave system in
a "Power Split" configuration is set to. It is suggested to leave this value at the default (60
seconds).
Rectifier
All Rect Set Menu
Menu Navigation: Main Menu / Settings / Rectifier / All Rect Set
Note: For WEB Interface; menu items are found under Device Information / Rectifier Group /
Settings Tab.