Emerson M820B Power Supply User Manual


 
UM1M820BNA User Instructions
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B)
Spec No. 1M820DNA (Model M820D)
108 Chapter 3. Local Display Menus
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
"Batt Group" Parameter Settings:
EQ/FLT Control*: Places the system in Equalize Charge or Float Charge mode.
BattTestControl*: Starts or stops a Battery Test.
Reset Batt Cap*: Resets the battery capacity calculation.
Clr Bad Bat Alm*: Clears a bad battery alarm.
Clr LiBatt Lost*: Clears a Li-Ion battery lost alarm.
ClrLiBatComFail*: Clears a Li-Ion battery communications fail alarm
Clear AbnlCur Alm*: Clears an abnormal current alarm.
Clear Cur Imb Alm*: Clears a current imbalance alarm.
ClrBatTestFail*: Clears a battery test fail alarm.
LVD
LVD Unit Menu
Menu Navigation: Main Menu / Manual / LVD / LVD Unit
Note: For WEB Interface; menu items are found under Device Information / LVD Group / LVD Unit
/ select the Control tab.
"LVD Unit" Parameter Settings:
LVD1 Control: Temporarily connects or disconnects LVD1. Setting returns to original
when Controller is returned to the Auto mode.
LVD2 Control: Temporarily connects or disconnects LVD2. Setting returns to original
when Controller is returned to the Auto mode.
EIB
EIB 1 Menu
Menu Navigation: Main Menu / Manual / EIB / EIB1
Note: For WEB Interface; menu items are found under Device Information / EIB Group / EIB 1 /
select the Control tab.
"EIB 1" Parameter Settings: (EIB1 refers to the first Extended Interface Board (EIB) in the
system.))
Relay Output 9 through 13: Temporarily sets the relay to active or not active. Setting
returns to original when Controller is returned to the Auto mode.
Converter
All Conv Ctrl Menu
Menu Navigation: Main Menu / Manual / Converter / All Conv Ctrl
Note: For WEB Interface; menu items are found under Device Information / Converter Group /
select the Control tab.
"All Conv Ctrl" Parameter Settings:
Converter Trim: Temporarily sets the output voltage for all converters. Setting reverts to
original when Controller is returned to the Auto mode.
DC On/Off Ctrl: Temporarily turns the DC output on or off for all converters. Setting returns
to original when Controller is returned to the Auto mode.
Conv LED Control: Temporarily sets whether or not a converter’s local power indicator
blinks when the Controller is communicating with the converter. Setting returns to original
when Controller is returned to the Auto mode.