Emerson M820B Power Supply User Manual


 
User Instructions UM1M820BNA
Spec No. 1M820BNA (Model M820B) Issue AH, March 4, 2013
Spec No. 1M820DNA (Model M820D)
Chapter 3. Local Display Menus 81
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
3.2.1 Adjustment Range Restrictions
Float Voltage Setting
Cannot be adjusted higher than EQ Voltage setting.
Cannot be adjusted lower than 1V (24V systems) or 2V (48V systems) above Under Voltage 1 Alarm”
setting or higher than 1V (24V systems) or 2V (48V systems) below Over Voltage 1 Alarm” setting.
EQ Voltage Setting
Cannot be adjusted lower than Float Voltage setting.
HVDS Limit
Cannot be adjusted lower than 0.5V above the EQ Voltage setting.
Under Voltage 1 Alarm Setting
Cannot be adjusted lower than Under Voltage 2 Alarm” setting.
Cannot be adjusted higher than Over Voltage 1 Alarm” setting.
Under Voltage 2 Alarm Setting
Cannot be adjusted higher than Under Voltage 1 Alarm” setting.
Over Voltage 1 Alarm Setting
Cannot be adjusted higher than Over Voltage 2 Alarm” setting.
Cannot be adjusted lower than Under Voltage 1 Alarm” setting.
Over Voltage 2 Alarm Setting
Cannot be adjusted lower than Over Voltage 1 Alarm” setting.
LVD1 and LVD2 Disconnect Setting
Cannot be adjusted higher than LVD Reconnect Voltage setting.
LVD1 and LVD2 Reconnect Setting
Cannot be adjusted lower than LVD Disconnect Voltage setting.