Local Menu Flow Diagrams
Battery
Basic
Charge
Test
Temp Comp
Capacity
Battery 1
NumBatt Shunts
1 (0-2)
Calc BattCurr
No (no /yes)
Low CapacityPt
75 % (25-100)
Current Limited
No (no /yes)
BTRMTempSensor
IB2T2 ( N one /SMTemp8T8 / ... /SMTemp8 T1/ ... /
SMTemp1 T8 /... /SMTemp1 T1/ EIBT2 /EIB T1 /
IB2T2 / IB2T1 /System T3/ SystemT2 / SystemT1 /
Average SMBRC /Average /Maximum)
BTRMTemp High2
100.0deg. C (0-100)
BTRMTemp High1
90.0 deg.C (0-100)
BTRMAction
Disabled (disabled /lower voltage)
BTRM Voltage
51.0 V (45-55) (22.5-27.5)
ABCLPoint
20A (1-60)
FloatVoltage
54.0 V (42.0-58.0)(21.0-29.0)
EQ Voltage
56.5 V (42.0-58.0)(21.0-29.0)
Batt CurrLimit
0.10 C10 (0.10-0.25)
Over CurrLmt
0.30 C10 (0.30-1.00)
Auto EQ
No (no /yes)
EQ Start Curr
0.060 C10 (0.040-0.080)
EQ Start Cap
80.0 % (0-99)
EQ StopCurr
0.010 C10 (0.002-0.020)
EQ StopDelay
180 min (0-1440)
Maximum EQTime
1080m in (60-2880)
Cyc EQ
No (no/yes)
Cyc EQ Interval
100 days (2-365)
Cyc EQ Duration
720 min (30-2880)
TestVoltLmt
45.0 V (43.0-53.5) (21.5-27.0)
TestEnd Volt
45.2 V (43.2-53.5) (21.5-27.0)
End TestTime
100 min (10-1440)
EndTestCapacity
70 % (0-100)
RecordThreshold
0.100 V (0.100-1.000)
AC FailTest
Disabled (disabled /enabled)
PlannedTests
0 (0-12)
Test 1(M-DH r)
10-21 10
Const Curr Test
Disabled (disabled /enabled)
ConstCurrTCurr
9999.0A (1-9999)
Short Test
Disabled (disabled /enabled)
ShortTestCycle
30 days (1-365)
Short Test Time
5 min (1-60)
Max DiffCurr
0.05 C10 (0.00-1.00)
BattTestLowCap
99 % (70-100)
Temp CompCenter
25.0 deg.C (0.0-40.0)
Temp Comp Coeff
72.0 mV/deg. C (0.0-500.0)
TempComp Sensor
None (None /SMTemp8T8 /.../ SMTemp8 T1 /.../
SMTemp1 T8/ .../ SMTemp1T1 /EIBT2 / EIB T1 /
IB2T2 /IB2 T1/ System T3/ SystemT2 /System T1/
AverageS MBRC/ Average/ Maximum)
CompTemp High2
60 deg. C (0-100)
CompTemp High1
50 deg. C (0-100)
CompTemp Low
-10.0 deg. C (-40 to +100)
Temp Comp Max V
29.0 (42.0-58.0) (21.0-29.0)
Temp Comp Clamp
Enabled (disabled /enabled)
Temp Comp Min V
26.0 (42.0-58.0) (21.0-29.0)
Charging Eff
96 % (10-100)
Time 0.1C10
10.00 h (0.00-10.00)
Time 0.2C10
4.90 h (0.00-10.00)
Time 0.3C10
3.00 h (0.00-10.00)
Time 0.4C10
2.00 h (0.00-10.00)
Time 0.5C10
1.40 h (0.00-10.00)
Time 0.6C10
1.20 h (0.00-10.00)
Time 0.7C10
1.10 h (0.00-10.00)
Time 0.8C10
0.90 h (0.00-10.00)
Time 0.9C10
0.70 h (0.00-10.00)
Time 1.0C10
0.50 h (0.00-10.00)
Rated Capacity
600.0Ah (50.0-50000.0)
ShuntCurrent
800.0A (50.0-50000.0)
ShuntVoltage
25.0 mv (1.0-150.0)
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ESC
B3
ENT
Basic
Charge
Test
Temp Comp
Capacity
Battery 1
To Change aParameter:
Press or to move up and
down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change.
Press ESC to cancel the change.
The parameter values shown in ( ) are the
adjustment range or acceptable values.
Factory default settings are listed in the
ACU+ Configuration Drawing (C-dwg)
furnished with your system.
To Select a Sub-Menu:
Press or to move cursor in
menu screen (selects menu item).
Press ENT to enter selected sub-menu.