Chapter 2. Operation 59
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Table 4
Full Alarm Name - WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description
Action to Correct
Mains Failure
(Mains Failure)
Commercial AC power failure.
Check why no commercial AC power.
OB AC Unit (OB-AC Module must be present in system)
(OBAC)
Phase A Over Voltage 1
(PH-A Over Volt1)
Phase A voltage is above over voltage
1 threshold.
Check why voltage is high.
Phase A Over Voltage 2
(PH-A Over Volt2)
Phase A voltage is above over voltage
2 threshold.
Phase A Under Voltage 1
(PH-A UnderVolt1)
Phase A voltage is below under
voltage 1 threshold.
Check why voltage is low.
Phase A Under Voltage 2
(PH-A UnderVolt2)
Phase A voltage is below under
voltage 2 threshold.
Phase B Over Voltage 1
(PH-B Over Volt1)
Phase B voltage is above over voltage
1 threshold.
Check why voltage is high.
Phase B Over Voltage 2
(PH-B Over Volt2)
Phase B voltage is above over voltage
2 threshold.
Phase B Under Voltage 1
(PH-B UnderVolt1)
Phase B voltage is below under
voltage 1 threshold.
Check why voltage is low.
Phase B Under Voltage 2
(PH-B UnderVolt2)
Phase B voltage is below under
voltage 2 threshold.
Phase C Over Voltage 1
(PH-C Over Volt1)
Phase C voltage is above over voltage
1 threshold.
Check why voltage is high.
Phase C Over Voltage 2
(PH-C Over Volt2)
Phase C voltage is above over voltage
2 threshold.
Phase C Under Voltage 1
(PH-C UnderVolt1)
Phase C voltage is below under
voltage 1 threshold.
Check why voltage is low.
Phase C Under Voltage 2
(PH-C UnderVolt2)
Phase C voltage is below under
voltage 2 threshold.
Mains Failure
(Mains Failure)
Commercial AC power failure.
Check why no commercial AC power.
Severe Mains Failure
(SevereMainsFail)
Commercial AC power voltage is too
low.
Check why voltage is low.
Mains Failure (Single)
(Mains Failure)
Commercial AC power failure.
Check why no commercial AC power.
Severe Mains Failure (Single)
(SevereMainsFail)
Commercial AC power voltage is too
low.
Check why voltage is low.