Gateway E-826R Network Card User Manual


 
Preparation
www.gateway.com
11
Choosing a location
Choose a location that meets the following criteria. The autoloader uses
standard rack mounting hardware and must be flat and level.
UL requirements
Elevated operating ambient temperature
When installed in a closed multi-unit rack assembly, the operating ambient
temperature of the rack environment may be greater than the room ambient
temperature. Therefore, consideration should be given to installing the
equipment in an environment compatible with the manufacturer’s maximum
recommended ambient temperature.
Reduced air flow
When you install the autoloader in a rack, make sure that there is adequate air
flow for safe operation.
Mechanical loading
When you install the autoloader in a rack, make sure that you do not load the
rack unevenly (for example, all of the equipment in the top section of the rack).
Criteria Description
Rack requirements Standard 19-inch rack with 2U (3.5 inches) of available rack space.
Room temperature 50–95° F (10–35° C)
Power source AC power voltage: 100–127 VAC; 200–240 VAC
Line frequency: 50–60 Hz
Locate the AC outlet near the autoloader. The AC power cable is the product’s
main disconnect device and must be easily accessible at all times.
Weight 31 lb. (14.1 kg) unloaded
38 lb. (17.2 kg) loaded with 2 magazines, 16 cartridges
Air Quality Minimize sources of particulate contamination. Avoid areas near frequently
used doors and walkways, cooling or exhaust vents, stacks of supplies that
collect dust, printers, and smoke-filled rooms.
Excessive dust and debris can damage tapes and tape drives.
Humidity 20–80% RH (non-condensing)
Clearance Back: Minimum of 17 inches (43.2 cm)
Front: Minimum of 27 inches (68.6 cm)
Sides: Minimum of 2 inches (5.08 cm)