Register Map for Process and Operation Type Variables
Miscellaneous Register Map
Revision 4 HC900 Hybrid Controller Communications User Guide 41
9/03
6.2 Miscellaneous Register Map
Table 6-2 Miscellaneous Register Map Addresses
Address
(hex)
Register
(decimal)
Parameter Name Access Notes
0000 0001 Instrument Mode R/W Bit Packed
Indicators:
Bit 0: 1:Diagnostic
Bit 1: 1: unused
Bit 2: 1:Maintenance/Offline mode
Bit 3: 1:Program mode
Bit 4: 1:Reset Unit/Force Cold Start
(Write Only)
Bit 5: 1:On-Line/Run mode
Bit 6…15: Unused
0002 0003 Load Recipe R/W Floating Point
Read: Returns zero
Write: Loads the recipe, identified in the
request, from the recipe pool.