Honeywell HC900 Network Card User Manual


 
Register Map for Process and Operation Type Variables
Scheduler Value Register Map
Revision 4 HC900 Hybrid Controller Communications User Guide 65
9/03
Procedure for Uploading Setpoint Schedules
Table 6-19 Steps to Upload a Setpoint Schedule using Modbus Function Codes 3, 6, 16
Step Action
1
Set the scheduler to RESET by writing any number to 12367 (304E). This can be done
either with function code 6 or 16.
2
Load the schedule into the setpoint scheduler block by writing the schedule number to
registers 12321 and 12322 (3020 and 3021). This is a floating point register and requires a
multiple register write (function code 16)
3
Read the header information desired -- registers 12331 (302A) - 12347 (303A) and register
12368 (304F) using function code 3.
4
Read the information for each segment desired using function code 3 -- registers 3200 -
322F for segment 1, 3230 - 325F for segment 2, etc.
This table contains Value Register addresses of SP Scheduler #1. See the Global Register Map - Table 6-1 for
starting and ending addresses (hex) for SP Scheduler #2
Table 6-20 Scheduler #1 Value Register Map Addresses
Address
(hex)
Register
(decimal)
Channel Number Access Notes
3000 12289 Scheduler Output 1 R Floating Point in Engineering Units.
3002 12291 Scheduler Output 2 R Floating Point in Engineering Units.
3004 12293 Scheduler Output 3 R Floating Point in Engineering Units.
3006 12295 Scheduler Output 4 R Floating Point in Engineering Units.
3008 12297 Scheduler Output 5 R Floating Point in Engineering Units.
300A 12299 Scheduler Output 6 R Floating Point in Engineering Units.
300C 12301 Scheduler Output 7 R Floating Point in Engineering Units.
300E 12303 Scheduler Output 8 R Floating Point in Engineering Units.
3010 12305 Scheduler Auxiliary Output 1 R Floating Point in Engineering Units.
3012 12307 Scheduler Auxiliary Output 2 R Floating Point in Engineering Units.
3014 12309 Scheduler Auxiliary Output 3 R Floating Point in Engineering Units.
3016 12311 Scheduler Auxiliary Output 4 R Floating Point in Engineering Units.
3018 12313 Scheduler Auxiliary Output 5 R Floating Point in Engineering Units.
301A 12315 Scheduler Auxiliary Output 6 R Floating Point in Engineering Units.
301C 12317 Scheduler Auxiliary Output 7 R Floating Point in Engineering Units.
301E 12319 Scheduler Auxiliary Output 8 R Floating Point in Engineering Units.