Honeywell HC900 Network Card User Manual


 
Register Map for Process and Operation Type Variables
Sequencer #1 Parameters Register Map
72 HC900 Hybrid Controller Communications User Guide Revision 4
9/03
6.19 Sequencer #1 Parameters Register Map
Summary
This table contains Parameter Map addresses of Sequencer #1. See the Sequencer Parameter Register
Maps - Table 6-23 for starting and ending addresses (hex) for Sequencer #2 through Sequencer #4
Parameter Map Addresses.
Table 6-26 Sequencer #1 Parameters Register Map Addresses
Address
(hex)
Register
(decimal)
Channel Number Access Notes
5AA0 23201 Not used N/A Not used
5AA1 23202 Save current sequence request R/W Integer, Saves current sequence to
archive and assigns it to the number
written (1-20).
5AA2 23203 Reset W Integer, Write to this location results in
reset action and data is ignored.
5AA3 23204 Run W Integer, Write to this location starts run
action and data is ignored.
5AA4 23205 Hold W Integer, Write to this location results in
reset action and data is ignored.
5AA5 23206 Advance W Integer, Write to this location results in an
advance to next step and data is ignored.
Writing to this register is only permissible
in the hold mode.
5AA6 23207 Not used N/A Not used
5AA7 23208 Step jumped to on Jog R/W Integer Step number for jog.
5AA8 23209 Current Sequence number R Integer Sequence number loaded.
5AA9 23210 Step Number R Integer value for current step number.
5AAA 23211 Load Sequence number R/W Integer, sequence number loaded to
sequencer. Writing to this register is only
permissible in the Ready mode.
5AAB 23212 Step number change request R/W Integer, go to a step number in any
mode.
5AAC 23213 Outputs R Integer, Bit packed for 16 output values
0:OFF 1:ON
5AAD 23214 Time units R/W Integer, 0=hrs, 1=minutes.
5AAE 23215 Elapsed Sequence Time R Floating point value for elapsed
sequence time in minutes.
5AB0 23217 Time Remaining in current step R Floating point value for time remaining in
current step in minutes.