Honeywell HC900 Network Card User Manual


 
Register Map for Process and Operation Type Variables
Set Point Programmer Value Register Map
56 HC900 Hybrid Controller Communications User Guide Revision 4
9/03
6.11 Set Point Programmer Value Register Map
This table contains Value Register addresses of SP Programmer #1. See the Global Register Map - Table
6-1 for starting and ending addresses (hex) for SP Programmer #2 through SP Programmer #8 Value
Register Map Addresses.
Table 6-13 Set Point Programmer #1 Value Register Map Addresses
Address
(hex)
Register
(decimal)
Channel Number Access Notes
1E00 7681 Set Point Programmer Output R Floating Point in Engineering Units.
1E02 7683 Current Segment Number R/W Floating Point; 1...Max Segment # 50
A write changes the segment number.
1E04 7685 Program Elapsed Time R Floating Point in Minutes
Continues to run when in Hold
1E08 7689 Segment Time Remaining R Floating Point in Minutes
1E0A 7691 Current Segment Events R Bit Packed
Indicates status of events 1-16 in one register
Bit 0: Event #1
:
Bit 15: Event #16
0: Event OFF 1: Event ON
1E0B 7692 Status R Bit Packed
Bit 0: 1=Ready
1: 1=Run
2: 1=Hold
3: 1=End
4: 1=Reserved
5: 1=Time Units in Minutes
6: 1=Time Units in Hours
7: Ramp Units
0: Time
1: Rate
8: Reserved
9: If bit 2 Set
0: Operator hold
1: Guaranteed soak hold
10: 0: Current segment is a soak
1: Current segment is a ramp
11-15: Reserved
1E0C 7693 Run W Signed 16 bit integer
Write to location Starts Profile;
Data ignored
1E0D 7694 Hold W Signed 16 bit integer
Write to location Holds Profile;
Data ignored