Honeywell HC900 Network Card User Manual


 
Register Map for Process and Operation Type Variables
Sequencer #1 Step 1 Table Register Map
Revision 4 HC900 Hybrid Controller Communications User Guide 73
9/03
Address
(hex)
Register
(decimal)
Channel Number Access Notes
5AB2 23219 Sequence status R Integer value for bit packed current
sequence state :
Bit 0 = Ready
Bit 1 = Run
Bit 2 =Hold
Bit 3 = Stop
Bit 4 = Disable
Bit 5 = time units (minutes)
Bit 6 = time units (hours)
5AB4 23221 State R Integer value for current state number
5AB6 23223 Auxiliary Output R Floating point value auxiliary output
6.20 Sequencer #1 Step 1 Table Register Map
Summary
This table contains Step #1 Table Map addresses of Sequencer #1. See the Sequencer Step 1 Table
Register Maps - Table 6-24 for starting and ending addresses (hex) for Sequencer #2 through Sequencer
#4 Step #1 Table Map Addresses.
Table 6-27 Sequencer #1 Step 1 Table Register Map Addresses
Address
(hex)
Register
(decimal)
Channel Number Access Notes
5AC0 23233 Time Next step R/W Integer value of the next step executed
when time expires.
5AC1 23234 Event1 Next step R/W Integer value of the next step executed
when configured event 1 transitions from
OFF to ON.
5AC2 23235 Event2 Next step R/W Integer value of the next step executed
when configured event 2 transitions from
OFF to ON.
5AC3 23236 Advance Next step R/W Integer value of the next step executed
when Advance transitions from OFF to
ON.
5AC4 23237 Step Time R/W Floating value for time of present step.
5AC6 23239 Auxiliary Output R/W Floating Auxiliary analog value
associated with the step.
Note: There are 64 instances of the step table (one for each step) for each Sequencer.
The addresses consumed by the full step table would be from 5AC0 thru 5CBFh.