16
Bit 0: Output #13 Enable: 0=NO, 1=YES
Bit 1: Output #13 Used: 0=NO, 1=YES
Bit 2: Output #13 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output # Enable: 0=NO, 1=YES
Bit 5: Output #14 Used: 0=NO, 1=YES
Bit 6: Output #14 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #15 Enable: 0=NO, 1=YES
Bit 9: Output #15 Used: 0=NO, 1=YES
Bit 10: Output #15 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #16 Enable: 0=NO, 1=YES
Bit 13: Output #16 Used: 0=NO, 1=YES
Bit 14: Output #16 ON: 0=OFF, 1=ON
Bit 15: Unused
6708 26377 Request Style R
Bit Packed:
Bit 0: Direct: 0=NO, 1=YES
Bit 1: Rotary: 0=NO, 1=YES
Bit 2: FOFO: 0=NO, 1=YES
Bit 3: Fixed: 0=NO, 1=YES
Bit 4-15: Unused
6709 26378 Direct Request W
Unsigned 16 Integer
Data Ignored
670A 26379 Rotary Request W
Unsigned 16 Integer
Data Ignored
670B 26380 First on/First off
Request
W
Unsigned 16 Integer
Data Ignored
670C 26381 Fixed Request W
Unsigned 16 Integer
Data Ignored
670D 26382 Advance Request W
This does not apply if current style is Direct or if
Advance Active configuration parameter is set to OFF
Unsigned 16 Integer
Data Ignored
670E 26383 Input Count R
Floating Point in Counts
6710 26385 Output On-Delay R/W
Floating Point in Seconds
6712 26387 Output Off-Delay R/W
Floating Point in Seconds
6714 26389 Input Enable (1-
16)
R/W
Bit Packed:
Bit 0: Device #1 Enable: 0=NO, 1=YES
Bit 1: Device #2 Enable: 0=NO, 1=YES
Bit 2: Device #3 Enable: 0=NO, 1=YES