Honeywell HC900 Network Card User Manual


 
Register Map for Process and Operation Type Variables
Alternator Group Register Map
Revision 4 HC900 Hybrid Controller Communications User Guide 79
9/03
Address
(hex)
Register
(decimal)
Parameter Name Access Notes
Bit 9: Output #3 Used: 0=NO, 1=YES
Bit 10: Output #3 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #4 Enable: 0=NO, 1=YES
Bit 13: Output #4 Used: 0=NO, 1=YES
Bit 14: Output #4 ON: 0=OFF, 1=ON
Bit 15: Unused
6705 26374 Output Status #5-8 R
Bit Packed:
Bit 0: Output #5 Enable: 0=NO, 1=YES
Bit 1: Output #5 Used: 0=NO, 1=YES
Bit 2: Output #5 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #6 Enable: 0=NO, 1=YES
Bit 5: Output #6 Used: 0=NO, 1=YES
Bit 6: Output #6 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #7 Enable: 0=NO, 1=YES
Bit 9: Output #7 Used: 0=NO, 1=YES
Bit 10: Output # ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #8 Enable: 0=NO, 1=YES
Bit 13: Output #8 Used: 0=NO, 1=YES
Bit 14: Output # ON: 0=OFF, 1=ON
Bit 15: Unused
6706 26375 Output Status #9-
12
R
Bit Packed:
Bit 0: Output #9 Enable: 0=NO, 1=YES
Bit 1: Output #9 Used: 0=NO, 1=YES
Bit 2: Output #9 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #10 Enable: 0=NO, 1=YES
Bit 5: Output #10 Used: 0=NO, 1=YES
Bit 6: Output #10 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #11 Enable: 0=NO, 1=YES
Bit 9: Output # Used: 0=NO, 1=YES
Bit 10: Output #11 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #12 Enable: 0=NO, 1=YES
Bit 13: Output #12 Used: 0=NO, 1=YES
Bit 14: Output #12 ON: 0=OFF, 1=ON
Bit 15: Unused
6707 26376 Output Status #13-
16
R
Bit Packed: