Honeywell HC900 Network Card User Manual


 
Register Map for Process and Operation Type Variables
Scheduler Value Register Map
Revision 4 HC900 Hybrid Controller Communications User Guide 67
9/03
Address
(hex)
Register
(decimal)
Channel Number Access Notes
3049 12362 Current Segment Events
(Bit Packed)
R Bit Packed
Indicates status of events
Bit 0: Event #1
: :
Bit 15: Event #15
0: Event OFF
1: Event ON
304A 12363 Status
(Bit Packed)
R Bit Packed
Bit 0: 1=Ready
1: 1=Run
2: 1=Hold
3: 1=End
4: 1=Time Units in Seconds
5: 1=Time Units in Minutes
6: 1=Time Units in Hours
7: If bit 2 Set
0: Operator hold
1: Guaranteed soak hold
8-15: Reserved
304B 12364 Start W Signed 16 bit integer
Write to location Starts Schedule;
Data ignored
304C 12365 Hold W Signed 16 bit integer
Write to location Holds Schedule;
Data ignored
304D 12366 Advance W Signed 16 bit integer
Write to location Advances Schedule;
Data ignored
304E 12367 Reset W Signed 16 bit integer
Write to location Resets Schedule;
Data ignored
304F 12368 Time Units R/W
Bit Packed
Bit 0: Reserved
2: hours
3-15: Unused