Honeywell HC900 Network Card User Manual


 
Register Map for Process and Operation Type Variables
Scheduler Value Register Map
66 HC900 Hybrid Controller Communications User Guide Revision 4
9/03
Address
(hex)
Register
(decimal)
Channel Number Access Notes
3020 12321 Current Program Number R/W Floating Point
Indicates the present schedule number in
use. This also allows entry of a schedule
number from the HC900 stored schedule
memory (if schedules have been stored in
the controller) and will retrieve the
schedule data for a display showing a SP
schedule segment table. Typically, when
recipes are downloaded from third party
software, this will be the number
generated by the Schedule Save Request
parameter
A write to this register loads the program
into the scheduler function block; if 0 is
written, the scheduler’s schedule is
cleared.
Writing to this register is only
permissible in reset or ready mode.
3022 12323 Current Segment Number R/W Floating Point; 1 thru Max Segment #
A write changes the segment number.
3024 12325 Program Elapsed Time R Floating Point in Time Units
Includes or runs when in Hold
3026 12327 Segment Time Remaining R Floating Point in Time Units
3028 12329 Schedule Save Request R/W Floating point.
Assigns profile parameters downloaded
to a schedule number such as 1. This is
required by the HC900 to be the last
parameter downloaded. This
overwrites what is in this HC900 SP
Schedule memory location on each
download of a new SP Schedule.
Saves the schedule into the archive.
Writing to this register is prohibited in the
run mode.
302A 12331 Guaranteed Soak Limit 1 R/W Floating Point
302C 12333 Guaranteed Soak Limit 2 R/W Floating Point
302E 12335 Guaranteed Soak Limit 3 R/W Floating Point
3030 12337 Guaranteed Soak Limit 4 R/W Floating Point
3032 12339 Guaranteed Soak Limit 5 R/W Floating Point
3034 12341 Guaranteed Soak Limit 6 R/W Floating Point
3036 12343 Guaranteed Soak Limit 7 R/W Floating Point
3038 12345 Guaranteed Soak Limit 8 R/W Floating Point
303A 12347 Jog Segment R/W Floating Point
Defines segment for schedule to jog
based on an enable to an input pin