Mitsubishi Electronics QJ71C24/-R2 Network Card User Manual


 
8 - 45 8 - 45
MELSEC-Q
8 UTILITY PACKAGE (GX Configurator-SC)
[Monitor items]
Monitor items
Setting value storage
buffer memory address
Reference section containing
detailed explanation
Operation status 2204
H
/2304
H
Execution result 2205
H
/2305
H
PLC CPU
monitoring
function
Number of transmission 2206
H
/2306
H
Monitoring condition arrival block No. 2207
H
/2307
H
Cycle time units designation 2040
H
/2140
H
Cycle time designation 2041
H
/2141
H
PLC CPU monitoring function designation 2042
H
/2142
H
PLC CPU monitoring transmission measure designation 2043
H
/2143
H
Transmission pointer 2044
H
/2144
H
Output count designation 2045
H
/2145
H
Constant cycle
transmission
Data No. for connection designation 2046
H
/2146
H
Number of registered word blocks designation 204D
H
/214D
H
Number of registered bit blocks designation 204E
H
/214E
H
PLC CPU abnormal monitoring designation 204F
H
/214F
H
No. n block monitoring device
Monitoring device designation
2050
H
/2150
H
to
20A1
H
/21A1
H
Head device No. designation
2051
H
-2052
H
/
2151
H
-2152
H
to
20A1
H
-20A2
H
/
21A1
H
-21A2
H
Read point designation
2053
H
/2153
H
to
20A3
H
/21A3
H
Condition agreement transmission
Monitoring condition designation
2054
H
/2154
H
to
20A4
H
/21A4
H
Monitoring condition value designation
2055
H
/2155
H
to
20A5
H
/21A5
H
Transmission pointer designation
2056
H
/2156
H
to
20A6
H
/21A6
H
Output count designation
2057
H
/2157
H
to
20A7
H
/21A7
H
Data No. for connection designation
2058
H
/2158
H
to
20A8
H
/21A8
H
PLC PCU abnormal monitoring designation
Condition agreement transmission
Transmission pointer
20E6
H
/21E6
H
Number of output designation 20E7
H
/21E7
H
Data No. for connection designation 20E8
H
/21E8
H
Chapter 2 of
User's Manual (Application)