Mitsubishi Electronics QJ71C24/-R2 Network Card User Manual


 
10 - 21 10 - 21
MELSEC-Q
10 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Error Contents
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
7F69H Parity error
Data does not match the parity bit setting.
A malfunction occurred in the network because the
power source of the partner station was on or off.
Noise occurs in the network.
When the multidrop was connected, data was
transmitted simultaneously by multiple devices.
P/S
Match the Q series C24 and
external device settings.
Clear the error information
according to the error
information initialization request
(YE/YF).
In addition, when
communicating data with the
non procedure protocol, execute
the INPUT instruction, and read
and discard the unnecessary
data.
Measure the noise.
When connecting the multidrop,
remove the interlock so that
data will not be transmitted
simultaneously by multiple
devices.
7F6A
H
Buffer full error
OS receive buffer overflowed and receive data was
skipped.
SIO
Use DTR and DC control and
perform data communications
so that the buffer does not
become full. (Perform RS CS
control when the modem
function is used.)
If the Read Request signal was
turned ON, execute read
immediately.
7F6B
H
CD signal control
error
Data was received when CD signal is OFF when
"CD terminal check enabled" was designated.
CHn
ERR.
Recheck the CD signal control
of the external device.
(Send while the CD signal is ON.)
Set "no CD terminal checking"
and perform communication.
7F6C
H
Transmission error
Data cannot be sent because the line is not
connected.
CHn
ERR.
Transmit data after line
connection processing on the
interface side that uses the
modem function.
7F91
H
to
7F96
H
7F98
H
to
7F9A
H
7F9DH
7F9E
H
7FA0H
to
7FA3
H
7FA8H
7FAA
H
to
7FAD
H
7FAF
H
to
7FB2
H
7FB5
H
7FB6H
7FB8
H
to
7FBC
H
7FC0
H
to
7FC4
H
System error The OS of the Q series C24 detected some error. ( 1)