Omron CVM1-CLK21 Network Card User Manual


 
313
Error Log Section 9-3
9-3 Error Log
The error log records errors that occur in the Controller Link Unit and the time
they occur. The error log can be read or cleared by using Programming
Devices, such as the Controller Link Support Software, the CX-Net, or Sup-
port Software for the CPU Unit (SYSMAC Support Software), or by using the
message service (FINS commands for the Controller Link Unit.)
9-3-1 Error Log Table
Errors are recorded in an error log table in the Unit’s RAM, with one record for
each error and a maximum of 39 records.
Errors of significance are also recorded in the Unit’s EEPROM so that when
the power to the Unit is turned OFF or reset, a record of the error will remain.
(The error log table in EEPROM automatically reads the Unit’s RAM when the
power is turned ON again.)
If the number of records exceeds 39, the oldest record will be deleted and the
most recent error recorded.
Error Log Table Configuration
Item Specification
No. of records 39 max.
Data code Binary (Times are in BCD)
Length of each record 10 bytes
Configuration of records Error code: 2 bytes (Refer to page 314)
Detail code: 2 bytes (Refer to page 314)
Time: 6 bytes (Refer to the following
page)
Record order From the oldest record to the most
recent.