Omron CVM1-CLK21 Network Card User Manual


 
348
Memory Areas Appendix B
CS/CJ CPU Bus Unit Duplication Error Flag
Bit A40113 is turned ON when two CS/CJ CPU Bus Units have been assigned the same unit number. The dupli-
cated unit number is indicated in A410.
CS/CJ CPU Bus Unit Error, Unit Number Flags
When an error occurs in a data exchange between the CPU Unit and an CS/CJ CPU Bus Unit, the CS/CJ CPU
Bus Unit Error Flag (A40207) is turned ON and the bit in A417 corresponding to the unit number of the Unit
where the error occurred is turned ON.
CS/CJ CPU Bus Unit Restart Bits
Bits A50100 through A50115 can be turned ON to reset CS/CJ CPU Bus Units number #0 through #15,
respectively. The Restart Bits are turned OFF automatically when restarting is completed.
CIO Area: CS/CJ CPU Bus Unit Area
The CS/CJ CPU Bus Unit Area (CIO Area) is allocated to CS/CJ CPU Bus Units according to the unit numbers
assigned to them, as shown below. Each Unit is allocated 25 words.
Error Information: CIO 1500 + 25 × (Unit No.) (See page 304.)
Polling Node Address, Startup Node Address: CIO 1500 + 25
× (Unit No.) + 1 (See page 304.)
Unit no. Words Unit no. Words
0 1500 to 1524 8 1700 to 1724
1 1525 to 1549 9 1725 to 1749
2 1550 to 1574 10 1750 to 1774
3 1575 to 1599 11 1775 to 1799
4 1600 to 1624 12 1800 to 1824
5 1625 to 1649 13 1825 to 1849
6 1650 to 1674 14 1850 to 1874
7 1675 to 1699 15 1875 to 1899
1: Network parameter error (In PLC's EEPROM)
1: Data link table error (in PLC's EEPROM)
1: Routing table error (in PLC's EEPROM)
1: PLC system setting error
1: EEPROM error
1: Duplicate node address setting error
1: Inconsistent network parameters
1: Communications controller send error
1: Communications controller hardware error
1: Error lo
g
exists
Polling node address Startup node address
Each node address is displayed in 2-digit BCD.