6-7SectionSetting Conditions for Communications with Host by Using Memory Switches
164
Press the Unit No. touch switch to display
the unit number to be set. Press the Comm.
Speed touch switch to display the commu-
nications speed, standard or 115.2-kbps
high-speed. (The Comm. Speed setting de-
termines which method of 1:N NT Link is
used.)
The setting option changes each time the
touch switch is pressed. In this example, se-
rial port A is used for a standard 1:N NT Link.
Press Quit.
The unit number and communications
speed are set.
Press the Set touch switch to the right of the
port at which the setting has been made.
In this example, serial port A is used.
• To quit the unit number/communications speed setting screen without confirm-
ing the unit number/communications speed settings, press the Abort touch
switch. The NT31/NT31C will return to the memory switch setting screen (4/4)
with the previous settings still in effect.
Reference: Unit numbers are numbers assigned to each PT when multiple PTs are con-
nected to one host, so that the host can identify the individual PTs. The units num-
bers that can be set differ according to the host model, as follows.
S C200HE(-ZE):
Unit numbers 0 to 3 (maximum of 4 PTs per host port)
S C200HG(-ZE), C200HX(-ZE):
Unit numbers 0 to 7 (maximum of 8 PTs per host port)
When making the settings, make sure there is no duplication of unit numbers
among PTs.
On completion of unit number/communications speed setting a, the
NT31/NT31C returns to the memory switch setting screen (4/4).
To set other memory switches, select the relevant screen using the [
] (next
screen) or [
] (previous screen) touch switch, then make the setting.
• To confirm the settings and quit the memory switch setting screen, press the
Quit touch switch. The settings made last will be set and the NT31/NT31C will
return to the MAINTENANCE MODE MENU screen.
• To quit the memory switch setting screen without confirming the settings, press
the Abort touch switch. The NT31/NT31C will return to the MAINTENANCE
MODE MENU screen with the previous settings still in effect.