Appendix CUsing an RS-232C/RS-422A Convertor Unit
263
Pin Arrangement
The convertor unit has a terminal block for an RS-422A/485 interface connection and a connector for an RS-232C
interface connection.
The pin arrangements for the RS-422A/485 terminal block and the RS-232C connector are as follows.
RS-422A/485 Terminal Block
Terminal
block pin
No.
Signal name Abbreviation
Signal direction
(convertor unit RS-422
device)
8 Request to send () CSA
7 Request to send (+) CSB
6 Receive data () RDA
5 Receive data (+) RDB
4 Send data () SDA
3 Send data (+) SDB
2 Signal ground SG (GND)
1 Functional ground
* The CSB and CSA signals are for specialized applications.
RS-232C Connector
Connector
pin No.
Signal name Abbreviation
Signal direction
(convertor unit RS-232C
device)
1 Not used
2 Send data SD
3 Receive data RD
4 Request to send
(shorted to CS internally)
RS
5 Clear to send
(shorted to RS internally)
CS
6 +5 V (150 mA) input for convertor
unit
+5 V
7 Data set ready
(shorted to ER internally)
DR
8 Data terminal ready
(shorted to DR internally)
ER
9 Signal ground SG